5. Diagnostics and error handling
5−24
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 6 ć Valve error
CPX error group 106 (CPX−MMI: [Error in valve] )
No.
Message
Cause/description
Error handling
Type
1)
60
Communication with valve
disturbed or valve not
available
Only the position measurĆ
ing system/sensor interĆ
face was found at
switch−on. The valve was
not detected.
·
Check the lines to the
valve.
·
Replace the valve.
Error level: F2
Reset: N
Communication between
CMAX and the valve was
interrupted.
·
Check the lines of the
axis string, valve and
sensor step−by−step and
exchange, if necessary.
61
Valve hardware is defecĆ
tive
The valve signals a hardĆ
ware error.
·
Replace the valve.
Error level: F2
Reset: N
Error while initialising the
valve.
·
Exchange the valve,
check the firmware
version of CMAX.
62
Overtemperature at valve
The valve signals overtemĆ
perature. (Ambient temĆ
perature too high).
·
Make sure there is
sufficient cooling.
Error level: F2
Reset: F
63
Valve jammed
The valve piston does not
move as expected.
·
Replace the valve.
·
Also check the air
quality (5 Ģ filter and
dry air).
Error level: F2
Reset: F
64
Valve load voltage outside
tolerance range (under−
voltage)
The valve signals a load
voltage which is too low.
Either the line between
CMAX and the valve is
defective or the valve is.
·
Check the cables on the
axis string.
·
Check the valve and exĆ
change, if necessary.
Error level: F2
Reset: F
1)
For the error level and reset type, see section 5.2.3.