4 leds on the sensor interface, Leds on the sensor interface – Festo Контроллер позиционирования CPX-CMAX User Manual
Page 155
5. Diagnostics and error handling
5−33
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
5.3.4
LEDs on the sensor interface
LEDs on the CASM−S−D2−R3
LED S1
LED S2
Status
CMAX error:
Green
Off
Ready for operation without errors.
ć
Green
Red
Initialising via CAN completed.
ć
Flashes green
Red
24 V present.
ć
Off
Off
24 V not available.
E80
Green
Flashes red
once
Error: Sensor error (supply voltage < 12 V for longer than
15 ms).
E82
Green
Flashes red
twice
Error: Sensor error (cable break in sensor cable or elecĆ
trical end position reached).
E87
Green
Flashes red
3 times
Error: Supply voltage (< 17 V for longer than 15 ms).
E85
Green
Flashes red
4 times
Error: Communication error (Bus Off" status).
E80
LEDs on the CASM−S−D3−R7
LED S1
LED S2
Status
CMAX error:
Green
Off
Ready for operation without errors.
ć
Green
Red
Initialising via CAN completed.
ć
Flashes green
Red
24 V present.
ć
Flashes green
Off
Not yet referenced.
ć (E10)
Off
Off
24 V unavailable.
E80
Green
Flashes red
once
Error: Sensor error.
E82
Green
Flashes red
twice
Error: Sensor cable (cable break in the sensor cable).
E87
Green
Flashes red
3 times
Error: Supply voltage (< 17 V for longer than 15 ms).
E85
Green
Flashes red
4 times
Error: Communication error (Bus Off" status).
E80