5. Diagnostics and error handling
5−22
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 5 ć System error B
CPX error group 105 (CPX−MMI: [System error B] )
No.
Message
Cause/description
Error handling
Type
1)
50
Operating pressure is too
low
2)
Pressure in both cylinder
chambers is < 1.5 bar.
·
Check the pressure
supply.
·
Wait until the cylinder
chambers are suffiĆ
ciently filled (possibly
via leakage through
valve).
·
Configure as warning.
Error
level: F2 (W)
Reset: F
51
Controller load voltage
outside tolerance range
(undervoltage)
Load voltage < 20 V for enĆ
abled controller or overĆ
load on axis string.
·
Check the valve load
supply (U
VAL
).
Error level: F2
Reset: F
52
Controller operating voltĆ
age outside tolerance
range (undervoltage)
Operating voltage < 18 V or
overload on axis string.
·
Check the operating
voltage supply for
electronics/sensors
(U
EL/SEN
).
Error level: F2
Reset: F
53
Controller: Overload load
supply
Short circuit in the cables
of the axis string (between
the controller and valve or
valve and sensor interĆ
face).
·
Check the cables and
modules in the axis
string (e.g. for a cable
breakage), replace if
necessary.
Error level: F2
Reset: F
Defect in the CMAX conĆ
troller.
·
Check CMAX and exĆ
change, if necessary.
Defect in the valve.
·
Check the lines and
valves step−by−step
and exchange, if
necessary.
Overload in valve outputs.
·
Check output connecĆ
tions and correct, if
necessary.
1)
For the error level and reset type, see section 5.2.3.
2)
Enable command, but no supply pressure.