5. Diagnostics and error handling

5−22

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

Malfunction group 5 ć System error B

CPX error group 105 (CPX−MMI: [System error B] )

No.

Message

Cause/description

Error handling

Type

1)

50

Operating pressure is too
low

2)

Pressure in both cylinder
chambers is < 1.5 bar.

·

Check the pressure
supply.

·

Wait until the cylinder
chambers are suffiĆ
ciently filled (possibly
via leakage through
valve).

·

Configure as warning.

Error
level: F2 (W)
Reset: F

51

Controller load voltage
outside tolerance range
(undervoltage)

Load voltage < 20 V for enĆ
abled controller or overĆ
load on axis string.

·

Check the valve load
supply (U

VAL

).

Error level: F2
Reset: F

52

Controller operating voltĆ
age outside tolerance
range (undervoltage)

Operating voltage < 18 V or
overload on axis string.

·

Check the operating
voltage supply for
electronics/sensors
(U

EL/SEN

).

Error level: F2
Reset: F

53

Controller: Overload load
supply

Short circuit in the cables
of the axis string (between
the controller and valve or
valve and sensor interĆ
face).

·

Check the cables and
modules in the axis
string (e.g. for a cable
breakage), replace if
necessary.

Error level: F2
Reset: F

Defect in the CMAX conĆ
troller.

·

Check CMAX and exĆ
change, if necessary.

Defect in the valve.

·

Check the lines and
valves step−by−step
and exchange, if
necessary.

Overload in valve outputs.

·

Check output connecĆ
tions and correct, if
necessary.

1)

For the error level and reset type, see section 5.2.3.

2)

Enable command, but no supply pressure.