beautypg.com

Festo Контроллер позиционирования CPX-CMAX User Manual

Page 70

background image

3. Electrical installation

3−10

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

CASM−S−D3−R7

Sensor interface for digital, incremental displacement encoders
with M12 displacement encoder connection (socket, 8 pin).

Pin

Allocation

S2

1

+ Ub sensor (5 V)

7

1

6

2

0 V

1

6

3

Sine signal +

5

8

4

Sine signal ć

4

3

2

5

Cosine signal ć

3

6

Cosine signal +

7

Screen

8

n.c. (not connected)

Housing

Earth terminal (FE)

The cable screening is connected to the earth terminal of the sensor
interface.

Tab. 3/7:

Pin allocation of connection S2 for the CASM−S−D3−R7

CASM−S−D2−R3

Sensor interface for analogue, absolute displacement encoders
(potentiometer), with M12 displacement encoder connection
(socket, 5 pin).

Pin

Allocation

S2

1

Displacement encoder housing

3

4

2

n.c. (not connected)

2

1

3

Analogue GND (AGND)

2

1

5

4

Reference voltage 5 V (REF 5V)

5

Analogue input 0 ... 5 V (INPUT)

Housing

Earth terminal (FE)

The cable screening is connected to the earth terminal of the sensor
interface.

Tab. 3/8:

Pin assignment of connection S2 for the
CASM−S−D2−R3