3. Electrical installation
3−13
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
3.4.1
Determining the current consumption
The current consumption of a CMAX system depends on the
number and type of the modules connected to the axis interĆ
face.
Recommendation:
·
Use a closed−loop regulated power supply.
·
When selecting the power supply unit, check that it proĆ
vides a sufficient output. Calculate the total current conĆ
sumption, if necessary.
Calculations
Tab. 3/10 and Tab. 3/11 show the current consumption for a
positioning system.
Observe the instructions on selecting the power supply unit
in the CPX system description.
CMAX current consumption from U
EL/SEN
of the
CPX terminal
Typical current consumption
200 mA
Maximum current consumption
300 mA
Tab. 3/10: Current consumption via U
EL/SEN
of the
CPX terminal
Current consumption from U
VAL
of the CPX terminal
Typical current consumption for the VPWP valve
1 A
Maximum current consumption for the VPWP voltage
output
0.5 A
Max. current consumption for the digital VPWP output
(clamping unit/brake)
0.5 A
Maximum total current consumption
2.5 A
Tab. 3/11: Current consumption from U
VAL
of the
CPX terminal