4. Commissioning

4−27

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

4. Step: Record is running

After the record start with SPOS.ACK = 1 has been detected,
CPOS.START can be reset.

Control bytes (step 4)

Bit

B7

B6

B5

B4

B3

B2

B1

B0

CCON

OPM2

OPM1

LOCK

ć

RESET

BRAKE

STOP

ENABLE

Byte 1

0

0

0

0

0

1/0

1

1

CPOS

ć

CLEAR

TEACH

JOGN

JOGP

HOM

START

HOLD

Byte 2

0

0

0

0

0

0

0

0

Record no. Record number of the next record to be started. Any
Byte 3

x

x

x

x

x

x

x

x

res.

Byte 4 ... 8: reserved (= 0)

The running record is signalled with SPOS.MC = 0.
Resetting CPOS.START is signalled back with SPOS.ACK = 0.

Status bytes (step 4)

Bit

B7

B6

B5

B4

B3

B2

B1

B0

SCON

OPM2

OPM1

FCT_MMI

24VL

FAULT

WARN

OPEN

ENABLED

Byte 1

0

0

0

1

0

0

1

1

SPOS

REF

STILL

DEV

MOV

TEACH

MC

ACK

HOLD

Byte 2

1

x

x

x

x

x

0

0

Record no. Acknowledgement of last started record: 36
Byte 3

0

0

1

0

0

1

0

0

RSB

ć

ć

XLIM

VLIM

RCE

COM1

RCC

RC1

Byte 4

x

x

x

x

x

x

x

x

Primary
actual
value

Byte 5 ... 8: Acknowledgement of the actual value of the position or force in the configured
system of units.