4. Commissioning

4−29

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

4.5.5

Direct mode

I/O diagram

t

min

t

min:

At least 1 bus cycle waiting time Recommendation: 1 PLC cycle

Not required if consistent data transmission is used

Setpoint values
Output data

Start
CPOS.START (B1)

Acknowledge start
SPOS.ACK (B1)

Motion complete
SPOS.MC (B2)

N − 1

N

N + 1

1

0

1

0

1

0

1

0

N + 2

1

2

3

4

Fig. 4/4:

Start the positioning job

The sequence of the remaining control and status bits
behave according to the record select operating mode.
See sections 4.5.4, Fig. 4/3.

1 The desired setpoint value (position, force) and the posiĆ

tioning condition (absolute/relative, speed or force ramp,
etc.) are set in the PLC output data.

2 With the rising edge at CPOS.START, CMAX accepts the

setpoint values, starts the positioning job, sets SPOS.MC
= 0 and acknowledges the starting edge with
SPOS.ACK = 1.