5 direct mode, Direct mode, 5 direct mode i/o diagram – Festo Контроллер позиционирования CPX-CMAX User Manual
Page 107
4. Commissioning
4−29
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
4.5.5
Direct mode
I/O diagram
t
min
t
min:
At least 1 bus cycle waiting time Recommendation: 1 PLC cycle
Not required if consistent data transmission is used
Setpoint values
Output data
Start
CPOS.START (B1)
Acknowledge start
SPOS.ACK (B1)
Motion complete
SPOS.MC (B2)
N − 1
N
N + 1
1
0
1
0
1
0
1
0
N + 2
1
2
3
4
Fig. 4/4:
Start the positioning job
The sequence of the remaining control and status bits
behave according to the record select operating mode.
See sections 4.5.4, Fig. 4/3.
1 The desired setpoint value (position, force) and the posiĆ
tioning condition (absolute/relative, speed or force ramp,
etc.) are set in the PLC output data.
2 With the rising edge at CPOS.START, CMAX accepts the
setpoint values, starts the positioning job, sets SPOS.MC
= 0 and acknowledges the starting edge with
SPOS.ACK = 1.