12 - 2
(4) Setting
Transmission speed, parity and stop bit should be set prior to transmission.
Set values before setting.
Transmission speed
: 300 bps
Parity
: None
Stop bit
: 1 bit
[Note] After setting, the set data in memory are backed up by built-in battery.
(5) Communication control
q
Method
Transmission of data with flow trasnmitter is made according to request command from host computer.
When a command is received from host computer, the data corresponding to the command is
transmitted from Portaflow to the host computer.
w
Commands
Commands with ASCII code are transmitted from host computer to flow transmitter.
The last code of 1 command is carriage return (0DH).
[Portaflow RS-232C Transmission Command Table]
Real time transmission
Command
DQ01 [CR]
Instantaneous flow (L/s or gal/s)
1.000E + 3
L/s
[CR] [CR]
DQ02 [CR]
Instantaneous flow (L/min or gal/min)
1.000E + 3
L/min
[CR] [CR]
DQ03 [CR]
Instantaneous flow (L/h or gal/h)
1.000E + 3
L/h
[CR] [CR]
DQ04 [CR]
Instantaneous flow (ML/d or Mgal/d)
1.000E + 3
ML/d
[CR] [CR]
DQ05 [CR]
Instantaneous flow (m
3
/s or ft
3
/s)
1.000E + 3
m3/s
[CR] [CR]
DQ06 [CR]
Instantaneous flow (m
3
/min or ft
3
/min) 1.000E + 3
m3/min
[CR] [CR]
DQ07 [CR]
Instantaneous flow (m
3
/h or ft
3
/h)
1.000E + 3
m2/h
[CR] [CR]
DQ08 [CR]
Instantaneous flow (Mm
3
/d or Mft
3
/d)
1.000E + 3
Mm3/d
[CR] [CR]
DQ09 [CR]
Instantaneous flow (BBL/s)
1.000E + 3
BBL/s
[CR] [CR]
DQ10 [CR]
Instantaneous flow (BBL/min)
1.000E + 3
BBL/min
[CR] [CR]
DQ11 [CR]
Instantaneous flow (BBL/h)
1.000E + 3
BBL/h
[CR] [CR]
DQ12 [CR]
Instantaneous flow (MBBL/d)
1.000E + 3
MBBL/d
[CR] [CR]
DV [CR] Instantaneous flow (m/s or ft/s)
32.00E + 1
m/s
[CR] [CR]
DI+ [CR]
Normal direction integration flow
+ TOTAL 1234567 mL
[CR] [CR]
DI- [CR]
Reverse direction integration flow
- TOTAL 0000123 mL
[CR] [CR]
DAO [CR]
Analog output
1.000E + 2 Analog Out
[CR] [CR]
DAI [CR]
Analog input
1.000E + 2 Analog In
[CR] [CR]
DC [CR]
Status
NORMAL
[CR] [CR]
(output of status comment of up to 20 characters)
DT [CR]
Time
95 - 01 - 05 12 : 00
[CR] [CR]
Data
Data format (example)
: space
Space for head of flow rate/velocity ( ) shows (-) at reverse flow.
BULLETIN F-68