7 - 1

7.1

Selection of mounting location

Detector mounting location, i.e., the conditions of the pipe subjected to flow rate measurement exert a
great influence on measurement accuracy. So select a location meeting the conditions listed below.

(1) There is a straight pipe portion of 10D or more on the upstream side and that of 5D or more on the

downstream side.

(2) No factors to disturb the flow (such as pump and valve) within about 30D on the upstream side.

7. MOUNTING OF DETECTOR

L

10D

Detector

L

50D

L

30D

Flow control valve exists on upstream side.

Flow control valve exists on downstream side.

L

10D

L

10D

L

10D

L

5D

L

30D

1.5D

L

50D

More than

0.5D

More than

10D

More than

10D

D

L

5D

L

5D

Check valve

P

Stop valve

More than 10D

90

°

bend

Tee

Diffuser

Reducer

Valves

Pump

Classification

For upstream side

For downstream side

Extracted from Japan Electric and Machinery Industry Society (JEMIS-032)

BULLETIN F-68