9.4

Setting of analog input/output (analog page)

This function allows you to set the measurement range, range, output mode, error handling for analog
input/output. It also allows you to perform output calibration.

9.4.1 Setting of analog input

(1) ADJUST: when performing zero adjustment and span adjustment for input

signals

[Operation]

q

Press the

or

key on the “ANALOG IN/

OUT” page and select “ADJUST” from

“INPUT”.

Press the

ENT

key, and you are ready to adjust

input signals.

w

Input 4 mA from an external and move the cursor

to “4 mA” by the

or

key. Then press the

ENT

key to perform zero adjustment.

e

Input 20 mA from the external and move the

cursor to “20 mA” by the

or

key. Then

press the

ENT

to perform span adjustment.

Red

(+)

Red (+)

Black

(-)

Black (-)

4 to 20mA

-

+

AO

(Output)

(Note) The connector should
be connected to
ANALOG IN/OUT

AI

(Input)

Indicator,
recorder,
regulator, etc.

Analog I/O cord (page 5-1)

Output load resistance: 0 to 1k

Input resistance:

100

ANALOG IN / OUT

INPUT

ANALOG

0 . 0 0 0 E 0

DISPLAY

INPUT RANGE

OUTPUT

DISPLAY

RANGE UNIT

OUTPUT RANGE

OUTPUT MODE

BURN-OUT

ADJUST

m/s

HOLD

1 . 0 0 0 E 0

0 . 8 - 4 - 2 0 m A

ADJUST

ADJUST

20mA

4mA

4mA

ESC

ADJUST