(6) ADJUST: when adjusting output circuit (prepare an ammeter)

q

Press the

or

key on the “ANALOG IN/OUT” page and select “ADJUST” from “OUTPUT”.

Press the

ENT

key, and the ADJUST screen is displayed, enabling you to calibrate the output circuit.

w

Select either 4 mA or 20 mA by the

or

key. Adjust the output circuit so that outputs are

adjusted to either 4 mA (0% output calibration) or 20 mA (100% output calibration) by pressing the

or

key.

e

Press the

ENT

key to set the outputs.

2 0 m A

ADJUST

4 m A

4 m A

ADJUST

ADJUST

ANALOG

4 m A

ADJUST

ANALOG

ANALOG

4 m A

ADJUST

2 0 m A

ADJUST

PUSH ENT KEY

ADJUSTED

ADJUSTED

2 0 m A

ADJUST

ENT

ENT

ENT

Adjust output to 20mA
and press .

Transition from
4 mA to 20 mA
or vice versa.

Adjust output
to 4 mA with
an ammeter
and press .

Press .

BULLETIN F-68