background image

4

ELECTRICAL CONNECTIONS

52

MFC 300

www.krohne.com

02/2012 - 4000498602 - MA MFC 300 R03 en

Pulse/frequency output passive, basic I/Os

• U

ext

≤ 32 VDC

• f

max

in operating menu set to f

max

≤ 100 Hz:

I ≤ 100 mA
open:
I ≤ 0.05 mA at U

ext

= 32 VDC

closed:
U

0, max

= 0.2 V at I ≤ 10 mA

U

0, max

= 2 V at I ≤ 100 mA

• f

max

in the operating menu set to 100 Hz < f

max

≤ 10 kHz:

I ≤ 20 mA
open:
I ≤ 0.05 mA at U

ext

= 32 VDC

closed:
U

0, max

= 1.5 V at I ≤ 1 mA

U

0, max

= 2.5 V at I ≤ 10 mA

U

0, max

= 5.0 V at I ≤ 20 mA

• If the following maximum load resistance R

L, max

is exceeded, the load resistance R

L

must be

reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R

L, max

= 47 kΩ

f ≤ 1 kHz: R

L, max

= 10 kΩ

f ≤ 10 kHz: R

L, max

= 1 kΩ

• The minimum load resistance R

L, min

is calculated as follows:

R

L, min

= (U

ext

- U

0

) / I

max

• Can also be set as status output; for the electrical connection refer to status output

connection diagram.

INFORMATION!

For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).

Compact and field housing versions:

Compact and field housing versions:

Compact and field housing versions:

Compact and field housing versions: Shield connected via the cable terminals in the terminal
compartment.
Wall-mounted version:

Wall-mounted version:

Wall-mounted version:

Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
(insulation to DIN 46245) in the terminal compartment.

Any connection polarity.

Figure 4-15: Pulse/frequency output passive P

p

.book Page 52 Monday, February 6, 2012 11:01 AM