ELECTRICAL CONNECTIONS

4

47

MFC 300

www.krohne.com

02/2012 - 4000498602 - MA MFC 300 R03 en

4.9.2 Wall-mounted housing, electrical connection of the inputs and outputs

1 Open the housing cover.
2 Push the cables through the cable entry and connect them to the supplied connector plugs 3.
3 Connect the shield if necessary.
4 Route the connector plugs with the clamped conductors into the sockets provided for that pur-

pose.

5 Close the housing cover.

DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!

INFORMATION!
Use shielded cables for frequencies above 100 Hz. The electrical connection of the shielding
must take place using 6.3 mm / 0.25" blade receptacles (insulation as per DIN 46 245) in the I/O
terminal compartment.

Figure 4-10: Terminal compartment for inputs and outputs in wall-mounted housing

INFORMATION!
Ensure that the housing gasket is properly fitted, clean and undamaged.

.book Page 47 Monday, February 6, 2012 11:01 AM