Operation – KROHNE MFC 300 EN User Manual
Page 116
6
OPERATION
116
MFC 300
www.krohne.com
02/2012 - 4000498602 - MA MFC 300 R03 en
Simulation of the measured values
S 2 Phase Flow
2 phase signal is above the programmed
threshold.
Check the process conditions (air).
S Interface PCB Fault
Error detected during self-monitoring of
interface card. Possible causes:
temperature in converter housing too high
or blown fuse.
Check whether the converter is exposed to
direct sunlight. Check the temperature in
Fct. B2.15. Replace electronic unit.
Messages on the display Description
Actions
Status: C _ _ _ _ _
Output values partially simulated or
fixed
Maintenance required.
C Checks In Progress
Test mode of the device. Measured values
are possibly simulated values or values with
fixed settings.
Message depending on the situation via
HART
®
or FDT. Depiction via display if
outputs are held by control input or set to
zero.
C Test XXXXX
Test of relevant unit activated.
C Standby Mode
Device is in standby mode.
Check control input settings in A8.
C Sensor Electronics
A test function in the sensor electronics (SE)
has been activated.
C Zero Calibration
Zero calibration performed. Flow
measurement interrupted.
Messages on the display Description
Actions
Status: S _ _ _ _ _
Out of specification, measurement
continues, accuracy possibly less.
Maintenance required.