Technical data – KROHNE MFC 300 EN User Manual
Page 142
8
TECHNICAL DATA
142
MFC 300
www.krohne.com
02/2012 - 4000498602 - MA MFC 300 R03 en
Control input
Control input
Control input
Control input
Function
Hold value of the outputs (e.g. for cleaning work), set value of the outputs to "zero",
counter and error reset, stop counter, range conversion, zero calibration
Start of dosing when dosing function is activated.
Operating data
Basic I/Os
Basic I/Os
Basic I/Os
Basic I/Os
Modular I/Os
Modular I/Os
Modular I/Os
Modular I/Os
Ex i
Ex i
Ex i
Ex i
Active
-
U
int
= 24 VDC
Ext. contact open:
U
0, nom
= 22 V
Ext. contact closed:
I
nom
= 4 mA
Contact closed (On):
U
0
≥ 12 V
with I
nom
= 1.9 mA
Contact open (Off):
U
0
≤ 10 V
with I
nom
= 1.9 mA
-
Passive
8 V ≤ U
ext
≤ 32 VDC
I
max
= 6.5 mA
at U
ext
≤ 24 VDC
I
max
= 8.2 mA
at U
ext
≤ 32 VDC
Contact closed (On):
U
0
≥ 8 V
with I
nom
= 2.8 mA
Contact open (Off):
U
0
≤ 2.5 V
with I
nom
= 0.4 mA
3 V ≤ U
ext
≤ 32 VDC
I
max
= 9.5 mA
at U
ext
≤ 24 V
I
max
= 9.5 mA
at U
ext
≤ 32 V
Contact closed (On):
U
0
≥ 3 V
with I
nom
= 1.9 mA
Contact open (Off):
U
0
≤ 2.5 V
with I
nom
= 1.9 mA
U
ext
≤ 32 VDC
I ≤ 6 mA at U
ext
= 24 V
I ≤ 6.6 mA at U
ext
= 32 V
On:
U
0
≥ 5.5 V or I ≥ 4 mA
Off:
U
0
≤ 3.5 V or I ≤ 0.5 mA
U
i
= 30 V
I
i
= 100 mA
P
i
= 1 W
C
i
= 10 nF
L
i
= 0 mH
NAMUR
-
Active to EN 60947-5-6
Terminals open:
U
0, nom
= 8.7 V
Contact closed (On):
U
0, nom
= 6.3 V
with I
nom
> 1.9 mA
Contact open (Off):
U
0, nom
= 6.3 V
with I
nom
< 1.9 mA
Detection of cable break:
U
0
≥ 8.1 V
with I ≤ 0.1 mA
Detection of cable short
circuit:
U
0
≤ 1.2 V
with I ≥ 6.7 mA
-