Operation – KROHNE MFC 300 EN User Manual
Page 121
OPERATION
6
121
MFC 300
www.krohne.com
02/2012 - 4000498602 - MA MFC 300 R03 en
6.8.5 Sensor levels A and B (menu B2.11, B2.12)
Normal display values:
• 80% for OPTIMASS 7000 - sizes 06…40 and OPTIMASS 1000 - sizes 15...40
• 60% for OPTIMASS 7000 - sizes 50...80
• 60% for OPTIMASS 1000 - size 50
• 60% for OPTIMASS 2000 - size 100
• 60% for OPTIMASS 8000 - all sizes
• 50% for OPTIMASS 2000 - size 150 and 250
• 40% for OPTIMASS 3000 - all sizes
6.8.6 2 phase signal (menu B2.13)
The value of the 2 phase signal can be read in this function. For applications that must detect 2
phase flow, an alarm level can be programmed. This alarm level depends on the application and
the process and can thus only be set on-site under current operating conditions during flow. For
detailed information refer to
2 phase threshold (Menu C1.5.3) on page 109.
6.8.7 SE board or BE board temperature (menu B2.14 or B2.15)
SE board temperature:
SE board temperature:
SE board temperature:
SE board temperature: indicates the temperature of the sensor electronics.
BE board temperature:
BE board temperature:
BE board temperature:
BE board temperature: indicates the temperature of the converter electronics
INFORMATION!
The sensor levels for A and B should not differ by more than 2%.