Weld cable test tab – Lincoln Electric IM8002 POWER WAVE MANAGER User Manual
Page 38

Chapter 6. Power Source Settings
Cable Settings and Tests
6.4
Power Wave® Manager User Manual
IM8002
Enable Negative Welding Polarity
If negative welding polarity is required for the Welding Power Source, such as in some Innershield™
applications, you may need to configure the correct voltage sense location manually.
NOTE |
If the system is already configured to sense arc voltage at
the remote voltage sense leads, no changes are required.
To enable negative welding polarity:
Procedure
Details
1.
Remove the check mark from the Automatic
hardware sense lead selection checkbox.
2.
Place a check mark in the Force negative
weld polarity checkbox.
3.
Click the Apply settings button
NOTE |
If the sense lead selection is specified
for a welding procedure, that selection will have
precedence over the settings you set here.
Therefore, some welding processes, such as TIG
(GTAW), stick (MMAW), and SMAW, will override
the Power Wave® Manager settings.
Weld Cable Test Tab
The Weld cable test tab (Figure 6.3) allows you to measure the resistance and the inductance of your
welding circuit. This can be used to determine how setup changes affect the welding circuit. In order to
run this test, the contact tip must be shorted to the work piece.
STOP |
Do not trigger the power source during this test.
The power source will be triggered for a short
time. Please verify output is turned off, and
short contact tip to work before proceeding.
Click the Perform test button to begin the inductance and resistance test.
STOP |
When you perform this test, the Welding Power Source’s
output will be turned on for a very short time (100
milliseconds).
Once the test is complete, Power Wave® Manager displays the values that were calculated based on the
downloaded weld trace. The resistance value appears in the Resistance field (measured in milliohms) and
the inductance value appears in the Inductance field (measured in microhenries) (Figure 6.3).