Is function block, 1 is function block schematic, Is function block -1 – Yokogawa YVP110 User Manual
Page 87: Is function block schematic -1
<17. IS Function Block>
17-1
IM 21B04C01-01E
17. IS Function Block
The function of the Input Selector (IS) block is to automatically select one signal from multiple input signals
using a specified selection method.
The IS block is used for selective control in which one measured quantity is selected from multiple measured
quantities to be transmitted to the controller as a controlled variable. This feature is primarily used for
temperature control systems.
17.1 IS Function Block Schematic
The following shows the Input Selector function block schematic.
IN_1
Configuration
Auto
Man
MODE
SELECTED
OUT
STATUS_OPTS
SELECT_TYPE
MIN_Good
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
DISABLE_1
DISABLE_2
DISABLE_3
DISABLE_4
DISABLE_5
DISABLE_6
DISABLE_7
DISABLE_8
OP_SELECT
F1701.ai
SELECTION
First Good
MINIMUM
MAXIMUM
MIDDLE
Latched Good
AVERAGE
Figure 17.1 IS Block
Input Parameters (Input Terms)
IN_1
: Block input 1
IN_2
: Block input 2
IN_3
: Block input 3
IN_4
: Block input 4
IN_5
: Block input 5
IN_6
: Block input 6
IN_7
: Block input 7
IN_8
: Block input 8
DISABLE_1 : Selector switch 1 to disable input 1 from being selected
DISABLE_2 : Selector switch 2 to disable input 2 from being selected
DISABLE_3 : Selector switch 3 to disable input 3 from being selected
DISABLE_4 : Selector switch 4 to disable input 4 from being selected
DISABLE_5 : Selector switch 5 to disable input 5 from being selected
DISABLE_6 : Selector switch 6 to disable input 6 from being selected
DISABLE_7 : Selector switch 7 to disable input 7 from being selected
DISABLE_8 : Selector switch 8 to disable input 8 from being selected
OP_SELECT : A parameter which can be set by an operator to forcibly employ the input of the selected
number