Relative
Index Index
Parameter Name
Default
(factory setting)
Write
Description
8
5008 SP
0
Auto
Indicates the setpoint for the block.
9
5009 OUT
0
Man
Indicates the output value and its status.
10
5010 SIMULATE
disable
Used to simulate the output from the Transducer
block; allows the user to set the value and status
input from the specified channel.
11
5011 PV_SCALE
0-100%
O/S
High and low scale values when displaying the
PV parameter and the parameters which have the
same scaling as PV.
12
5012 XD_SCALE
0-100%
O/S
High and low scale values used with the value
obtained from or sent to the transducer block for a
specified channel.
13
5013 GRANT_DENY
0
Option to control access from the host computer
and local control panel to tuning and alarm
parameters.
14
5014 IO_OPTS
0x000A
O/S
Settings for the I/O processing of the block
15
5015 STATUS_OPTS
0x0000
O/S
Defines block actions depending on block status
conditions.
16
5016 READBACK
—
—
Readback signal of valve position from transducer
block
17
5017 CAS_IN
—
Cascade input.
18
5018 SP_RATE_DN
+INF
Rate-of-decrease limit for SP effective in AUTO,
CAS, and RCAS modes. If this parameter is 0, no
limit is applied to the rate of decrease.
19
5019 SP_RATE_UP
+INF
Rate-of-increase limit for SP effective in AUTO,
CAS, and RCAS modes. If this parameter is 0, no
limit is applied to the rate of increase.
20
5020 SP_HI_LIM
100
Upper limit for setpoint (SP)
21
5021 SP_LO_LIM
0
Lower limit for setpoint (SP)
22
5022 CHANNEL
1
O/S
Defines the channel number of the hardware
channel connected to the transducer block.
Always set to 1 for the AO block in a YVP110.
23
5023 FSTATE_TIME
0 second
Defines the time from when the fault state of
the RCAS_IN or CAS_IN is detected to when
the output should be set to the level preset in
FSTATE_VAL (this action takes place only if Fault
State to value is set as true in I/O_OPTS).
24
5024 FSTATE_VAL
0
Preset output level for fault state. See above.
25
5025 BKCAL_OUT
—
—
Value to be input to BKCAL_IN of the downstream
block; used by the downstream block to prevent
reset windup and perform bumpless transfer to
closed-loop control.
26
5026 RCAS_IN
—
Remote cascade setpoint set by the host
computer, etc.
27
5027 SHED_OPT
1
Defines the mode shedding action to be taken
upon occurrence of time-out of communication in
a mode using the remote setpoint.
28
5028 RCAS_OUT
—
—
Remote setpoint sent to a host computer, etc.
29
5029 UPDATE_EVT
—
—
Shows the contents of an update event upon
occurrence.
30
5030 BLOCK_ALM
—
—
Shows the contents of a block alarm upon
occurrence.