Appendix 1. function block parameters, A1.1 parameters of resource block, A1.1 – Yokogawa YVP110 User Manual
Page 112
A-1
IM 21B04C01-01E
Appendix 1. Function Block Parameters
NOTE: Throughout the following tables, the Write column shows the modes in which the respective
parameters can be written. The legends of the entries are as follows:
O/S: Can be written when the corresponding block is in O/S mode.
Man: Can be written when the corresponding block is in Man mode.
Auto: Can be written when the corresponding block is in Auto, Man, or O/S mode.
— :
Can be written in no mode of the corresponding block.
Blank: Can be written in all modes of the corresponding block.
A1.1 Parameters of Resource Block
Relative
Index Index
Parameter Name
Default
(factory setting)
Write
Description
0
1000 Block Header
Block Tag
=O/S
Information about this block, including the block
tag, DD revision, execution time
1
1001 ST_REV
0
—
Incremented when a change is made to the
parameter settings for the resource block to
indicate the revision level of the settings, and
used to see whether or not there is a change in
parameter settings.
2
1002 TAG_DESC
Null
Universal parameter storing the description of the
tag
3
1003 STRATEGY
1
Universal parameter used by an upper-level
system to classify the function blocks.
4
1004 ALERT_KEY
1
Universal parameter used as a key to identify
the point from which an alert is issued; normally
used by an upper-level system to select alerts
to provide to a particular operator who covers a
specific area of the plant.
5
1005 MODE_BLK
O/S
Auto
Universal parameter that indicates the block
operation conditions and is composed of actual
mode, target mode, permitted modes, and normal
mode.
6
1006 BLOCK_ERR
—
—
Universal parameter indicating the hardware and
software error statuses related to the block itself
7
1007 RS_STATE
—
—
Indicates the statuses of resource in the YVP110.
8
1008 TEST_RW
Null
Parameter used to test read and write access to
the YVP110
9
1009 DD_RESOURCE
Null
—
Name of the device description (DD) containing
the information of this resource block
10
1010 MANUFAC_ID
0x00594543
—
Manufacturer ID; 5850435 (= 0x594543) is
assigned to Yokogawa Electric Corporation.
11
1011 DEV_TYPE
—
ID number of device; 1 or 7 (/EE) is assigned to
the YVP110.
12
1012 DEV_REV
—
Revision number of the YVP110
13
1013 DD_REV
—
Revision number of the device description (DD)
applied to this YVP110
14
1014 GRANT_DENY
0
Option to control access from the host computer
and local control panel to tuning and alarm
parameters
15
1015 HARD_TYPES
Scalar input,
Scalar output
Discrete input
—
Bit string indicating the hardware types
Bit 0: Scalar input
Bit 1: Scalar output
Bit 2: Discrete input
Bit 3: Discrete output