Relative
Index Index
Parameter Name
Default
(factory setting)
Write
Description [Setting range]
57
2057 MEAS_PRESS_
SUPPLY
0kPa
—
Air supply pressure (%); a parameter set by auto
tuning (Valid when an optional pressure sensor is
specified.)
58
2058 MEAS_SPRING_
RANGE
0kPa
—
Spring range of valve; a parameter set by auto
tuning (Valid when an optional pressure sensor is
specified.)
59
2059 CONTROL_DIR
2
—
Defines the acting direction of the feedback loop:
1 = direct
2 = reverse
60
2060 THETA_HI (*1)(*2)
+ 0.2 rad.
—
Upper angle signal limit of position sensor (in
radians)
61
2061 THETA_LO (*1)(*2)
-0.2 rad.
—
Upper angle signal limit of position sensor (in
radians)
62
2062 THETA_P (*1)(*2)
0 rad.
—
Angle signal equal to 50 % from position sensor
(in radians)
63
2063 TRAVEL_CALIB_
EXEC
1
O/S
Switch for starting a travel calibration.
64
2064 TRAVEL_CALIB_
RESULT
1
—
Indicates the result of a travel calibration.
65
2065 OPEN_STOP_ADJ
—
—
Not used for YVP110.
66
2066 AUTO_TUNE_EXEC 1
O/S
Switch for starting auto tuning.
67
2067 AUTO_TUNE_
RESULT
1
—
Indicates the result of auto tuning.
68
2068 AUTO_TUNE_STATE 0
—
Indicates auto tuning sequence number.
69
2069 SERVO_RET_TO_
DFLT
1
O/S
Writing 2 to this parameter resets all control
parameters to the defaults:
1 = off
2 = set (to the defaults)
70
2070 ADVAL_FW
—
—
Digital value of valve control signal, setpoint
equivalent to A/D value of valve position signal.
71
2071 ADVAL_BW
—
—
A/D value of valve position signal
72
2072 ADVAL_PRESS
—
—
A/D value of pressure from sensor
73
2073 ADVAL_T
—
—
A/D value of temperature from sensor
74
2074 TOTAL_CYCLE_
COUNT
0
O/S
Total number of cycles. To reset the count, write 0.
75
2075 CYCLE_DEADBAND 0.25%
—
Dead band of cycle counting
76
2076 CYCLE_COUNT_LIM 2^32-1
High-limit alarm setting for TOTAL_CYCLE_
COUNT. When TOTAL_CYCLE_COUNT has
reached this setting, a block alarm is generated.
77
2077 TOTAL_TRAVEL
0
O/S
Total amount of travel. To reset the count, write 0.
78
2078 TRAVEL_
DEADBAND
0.25%
Dead band of travel integration
79
2079 TRAVEL_LIM
2^32-1
High-limit alarm setting for TOTAL_TRAVEL.
When TOTAL_TRAVEL has reached this setting,
a block alarm is generated.
80
2080 TOTAL_OPEN_TIME 0 hour
Total time other than counted for TOTAL_CLOSE_
TIME. To reset the count, write 0.
81
2081 TOTAL_CLOSE_
TIME
0 hour
Total time where valve position is equal to or less
than OPEN_CLOSE_THRESHOLD. To reset the
count, write 0.
82
2082 OPEN_CLOSE_
THRESHOLD
0.25%
—
Threshold value for TOTAL_OPEN_TIME and
TOTAL_CLOSE_TIME.
83
2083 OPEN_TIME_LIM
2^32-1 hours
High-limit alarm setting for TOTAL_OPEN_TIME.
When TOTAL_OPEN_TIME has reached this
setting, a block alarm is generated.
84
2084 CLOSE_TIME_LIM
2^32-1 hours
High-limit alarm setting for TOTAL_CLOSE_TIME.
When TOTAL_CLOSE_TIME has reached this
setting, a block alarm is generated.