Relative
Index Index
Parameter Name
Default
(factory setting)
Write
Description [Setting range]
9
2009 TRANSDUCER_
DIRECTORY
1, 10
—
Index to the text describing the transducer
contained in the YVP110 positioner
10
2010 TRANSDUCER_
TYPE
106
—
Transducer type
11
2011 XD_ERROR
0
—
Stores the error prioritized at the highest level
from among the errors that are currently occurring
in the transducer block.
12
2012 CORRECTION_
DIRCTORY
1, 13
—
Stores the number of data collection and the index
number to be started with.
13
2013 FINAL_VALUE
—
O/S
Stores the valve control level and status written by
the AO block.
14
2014 FINAL_VALUE_
RANGE
-10%, 110%
O/S
Defines the upper and lower range limits of
FINAL_VALUE, and the unit code and decimal
point position for value indication of FINAL_
VALUE.
15
2015 FINAL_VALUE_
CUTOFF_HI
110%
O/S
If the value of FINAL_VALUE is greater than the
value set in this parameter, the YVP110 moves
the valve to the full-open position. There is a
hysteresis of 1% at the release time. If the value of
FINAL_VALUE becomes 1% less than the value
set in this parameter, this function is released.
16
2016 FINAL_VALUE_
CUTOFF_LO
0%
O/S
If the value of FINAL_VALUE is less than the
value set in this parameter, the YVP110 moves
the valve to the shut-off position. There is a
hysteresis of 1% at the release time. If the value
of FINAL_VALUE becomes 1% greater than
the value set in this parameter, this function is
released.
17
2017 FINAL_POSITION_
VALUE
—
—
Stores the position data read by the valve position
sensor.
18
2018 SERVO_GAIN (*1)
120
O/S
Static control loop gain set by auto tuning [0.5 to
1300 ]
19
2019 SERVO_RESET (*1) 15 sec
O/S
Integral time set by auto tuning
20
2020 SERVO_RATE (*1)
0. 22 sec
O/S
Derivative time set by auto tuning
21
2021 ACT_FAIL_ACTION 1
O/S
Specifies the actuator action direction (in case of
losing of air supply pressure):
1 = Air to Open
2 = Air to Close
22
2022 ACT_MAN_ID
0
—
ID of actuator manufacturer
23
2023 ACT_MODEL_NUM Null
—
Model number of actuator
24
2024 ACT_SN
0
—
Serial number of actuator
25
2025 VALVE_MAN_ID
0
—
ID of valve manufacturer
26
2026 VALVE_MODEL_
NUM
Null
—
Model number of valve
27
2027 VALVE_SN
0
Serial number of valve
28
2028 VALVE_TYPE
1
O/S
Valve type:
1 = linear-motion valve
2 = rotary-motion valve
29
2029 XD_CAL_LOC
Null
Shows and is used to record the location where
the positioner was calibrated.
30
2030 XD_CAL_DATE
01/01/00
Shows and is used to record the date when the
positioner was calibrated.
31
2031 XD_CAL_WHO
Null
Shows and is used to record the person who
calibrated the positioner.
32
2032 ALARM_SUM
Shows the alarm summary (current alarm
statuses, acknowledged/unacknowledged states,
masking states) for the transducer block.