A1.6 parameters of pid block (optional), A1.6, A-12 – Yokogawa YVP110 User Manual
Page 123
A-12
IM 21B04C01-01E
A1.6 Parameters of PID Block (Optional)
Index: PID1: 8000 through 8065
PID2: 8100 through 8165
Relative
Index Index
Parameter
Name
Default
(factory setting)
Write
Description
0
8000 BLOCK
HEADER
Block tag
= O/S
Information about this block, including the block tag, DD
revision, execution time.
1
8001 ST_REV
0
—
Incremented when a change is made to the parameter
settings for the PID block to indicate the revision level of
the settings, and used to see whether there is a change
in parameter settings.
2
8002 TAG_DESC
Spaces
Universal parameter storing the description of the tag.
3
8003 STRATEGY
1
Universal parameter used by an upper-level system to
classify the function blocks.
4
8004 ALERT_KEY 1
Universal parameter used as a key to identify the point
from which an alert is issued; normally used by an upper-
level system to select alerts to provide to a particular
operator who covers a specific area of the plant.
5
8005 MODE_BLK
O/S
Universal parameter that indicates the block operation
conditions and is composed of actual mode, target
mode, permitted modes, and normal mode.
6
8006 BLOCK_ERR —
—
Indicates the error statuses related to the block itself.
7
8007 PV
—
—
Indicates the primary analog value (or the corresponding
process value) used to execute the specified actions,
and the status of that value.
8
8008 SP
—
Auto
Setpoint of the block.
9
8009 OUT
—
Man
Value and status of output.
10
8010 PV_SCALE
0-100%
O/S
Upper and lower scale limit values used for scaling of the
input (IN) value.
11
8011
OUT_SCALE 0-100%
O/S
Upper and lower scale limit values used for scaling
of the control output (OUT) value to the values in the
engineering unit.
12
8012 GRANT_
DENY
0
Option to control access from the host computer and
local control panel to tuning and alarm parameters.
13
8013 CONTROL_
OPTS
0x0000
O/S
Defines block actions depending on block status
conditions.
14
8014 STATUS_
OPTS
0x0000
O/S
Defines options for control actions of block.
15
8015 IN
0
Controlled-value input.
16
8016 PV_FTIME
0
Time constant (in seconds) of the first-order lag filter
applied to IN.
17
8017 BYPASS
1
Man
Determines whether to bypass control computation.
1 = off; do not bypass.
2 = on; bypass.
18
8018 CAS_IN
0
Cascade setpoint.
19
8019 SP_RATE_
DN
+INF
Rate-of-decrease limit for setpoint (SP).
20
8020 SP_RATE_UP +INF
Rate-of-increase limit for setpoint (SP).
21
8021 SP_HI_LIM
100
Upper limit for setpoint (SP).
22
8022 SP_LO_LIM
0
Lower limit for setpoint (SP).
23
8023 GAIN
1
Proportional gain (= 100 / proportional band).
24
8024 RESET
10
Integration time (seconds).
25
8025 BAL_TIME
0
Unused.
26
8026 RATE
0
Derivative time (seconds).
27
8027 BKCAL_IN
0
Readback of control output.
28
8028 OUT_HI_LIM 100
Upper limit for control output (OUT).
29
8029 OUT_LO_LIM 0
Lower limit for control output (OUT).
30
8030 BKCAL_HYS 0
Hysteresis for release from a limit for OUT.status.
31
8031 BKCAL_OUT —
—
Read-back value to be sent to the BKCAL_IN of the
downstream block.
32
8032 RCAS_IN
0
Remote setpoint set from the host computer.