IAI America RCM-GW-DV User Manual
Page 74
68
DeviceNet Gateway
I/O Signal Details
Signal type
Bit
Signal
name
Description Details
Target
position
data
32-bit
data
---
Set a signed 32-bit integer (unit: 0.01 mm) based
on hexadecimal notation
Example) To specify +25.4 mm, set “Hex0009EC”
(“2540” in decimal notation).
The maximum settable value is +9999.99 mm =
999999 (decimal value) = 0F423FH
(hexadecimal value).
A negative value is indicated by a two’s
complement. Accordingly, the most significant bit
becomes “1.”
7.3 (5)
Movement
data
position
number
16-bit
data
PC***
When setting movement data other than position
data in the position table, specify the applicable
position number using a hexadecimal value.
7.2 (11)
7.3 (5)
b15
BKRL
Forced brake release
7.2 (18)
b14-b13
---
Cannot be used.
---
b12
SON
Servo on command
7.2 (7)
b11
STP
Pause command
7.2 (5)
b10
HOME
Home return command
7.2 (8)
b9
CSTR
Start command
7.2 (9)
b8
RES
Reset command
7.2 (4)
PLC output
Control
signal
b7-b0
---
Cannot be used.
---
Current
position
data
32-bit
data
---
The current position data is output as a signed 32-
bit integer (unit: 0.01 mm) based on hexadecimal
notation.
7.3 (5)
b15-b9
---
Cannot be used.
---
b8
PMSS
PIO/Modbus switching status
0: PIO, 1: Modbus
A PIO/Modbus switching command is used to
switch between the two modes.
---
b7
EMGS
Emergency stop status
7.2 (2)
b6 PSEL
Missed
work
---
b5
PWR
Controller ready
7.2 (1)
b4
SV
Ready (servo is on)
7.2 (7)
b3 MOVE
Moving
7.2
(6)
b2
HEND
Home return complete
7.2 (8)
b1
PEND
Position complete
7.2 (10)
PLC input
Status
signal
b0 ALM
Alarm
7.2
(3)