DeviceNet

Note



Note on DeviceNet Products



Take note that the IAI products listed below cannot be connected to Omron’s PLCs via DeviceNet.

[IAI products subject to this limitation]

Controller

All X-SEL models

Tabletop actuator

TT series

Gateway unit

RCM-GW-DV

* Units shipped on or after July 30, 2008

[Omron products subject to this limitation]

DeviceNet master unit

C200HW-DRM21-V1
CVM1-DRM21-V1

* Units manufactured in or before September 2008

Master units manufactured in or after October 2008 can be connected to the aforementioned
IAI products via DeviceNet.

[Cause]

Communication disharmony

[Action]

Use a PLC of a different type not subject to the above limitation. If you wish to use the DeviceNet
master unit C200HW-DRM21-V1 or CVM1-DRM21-V1, select a unit manufactured in or after October
2008. If changing the PLC is difficult, contact the IAI sales office near you or our customer center
“EIGHT.”