4 setting up the gateway unit, 1) setting the gateway unit mode, 1) setting the unit number – IAI America RCM-GW-DV User Manual
Page 126: 2) setting the node address, 3) setting the baud rate, etc, 6 assigning the master plc address, Setting up the gateway unit, Setting up the devicenet master unit (cj1w-drm21), Assigning the master plc address
120
DeviceNet Gateway
9.4
Setting Up the Gateway Unit
(1) Setting the Gateway Unit mode
Since the actuators are operated in the position-number specification mode, set each position of the
mode setting switch (SW1) as follows:
1: OFF 2: ON 3: OFF 4: OFF
(2) Setting the node address and baud rate for the Gateway Unit
Node address = 0
Baud rate = 500 kbps (example)
To effect the above settings, set the DIP switches as follows:
DR1: ON DR2: OFF
NA1, 2, 4, 8, 16, 32: All OFF
9.5
Setting Up the DeviceNet Master Unit (CJ1W-DRM21)
(1) Setting the unit number
On the PLC, set “0” indicating a CPU high-function unit.
(2) Setting the node address
Set the master unit’s node address on the network to “63” to prevent duplication with other slaves
within the range of 0 to 63.
(3) Setting the baud rate, etc.
The baud rate is set to 500 kbps. Accordingly, set the DIP switches as follows:
1: OFF 2: ON 3: OFF 4: OFF
* For details, refer to the operation manual for your PLC.
9.6
Assigning the Master PLC Address
Each slave (gateway unit) must be assigned to an I/O memory area of the CPU unit in which the
master unit is installed.
This assignment is performed either by free assignment where the DeviceNet configurator is used to
automatically assign an I/O memory area, or by fixed assignment using CX-Programmer. (Refer to
8.4 and 8.5.)