51

DeviceNet Gateway


I/O Signal List

Signal type

Bit

Signal

name

Description

15 MON

SIO link communication will start when this signal is turned ON, and
stop when it is turned OFF.
Do not turn the MON signal ON when CFG15 to 0 (linked axis
connection) are all OFF.
Also, do not turn all of CFG15 to 0 OFF when the MON signal is ON.
If CFG15 to 0 are all turned OFF and the MON signal turned ON, the
Gateway Unit will generate a SIO link error and the LED (T.ER) on the
front face of the unit will illuminate.

14-8 ---

These bits cannot be used.
Always set them to OFF (0).

7 NPS4

6 NPS3

5 NPS2

4 NPS1

3 NPS0

These bits are used in the command specification mode.
In any other mode, always set them to OFF (0).
Set the number of axes (0 to 16) used via positioner operation, using
a five-bit binary value. *1

2 PPS2

1 PPS1

Control

signal 0

0 PPS0

These bits are used in the command specification mode.
In any other mode, always set them to OFF (0).
Set the I/O pattern (pattern 0 to 4) of each axis to be used via
positioner operation, using a three-bit binary value. *2

15

CFG15

Link ON Axis No. 15

14 CFG14

14

13 CFG13

13

12 CFG12

12

11 CFG11

11

10 CFG10

10

9 CFG9

9

8 CFG8

8

7 CFG7

7

6 CFG6

6

5 CFG5

5

4 CFG4

4

3 CFG3

3

2 CFG2

2

1 CFG1

1

PLC output

Control

signal 1

0 CFG0

0

Specify the axis number corresponding to
each axis to be linked.
The axis will be connected when the signal is
turned ON (1), and disconnected when it is
turned OFF (0).
ON/OFF switching is permitted even when the
MON signal is ON.
(Notes)

Do not turn ON the axis number signal

corresponding to any axis not physically
connected.

Do not turn ON any axis number signal

other than the specifiable number selected
by the mode setting switch.

If either of the above conditions is breached, a
SIO link error will occur.

*1 If the mode setting switch (SW1) is set to the command specification mode and the settings of NPS0 to

NPS4 indicate 0, all axes will become simple direct operation axes.

*2 Only one I/O pattern of 0 to 4 can be used for positioner operation axes.