Page 123

background image

117

DeviceNet Gateway

8.5

Assigning the Master PLC Address by Fixed Assignment


Area 1 (3200CH to 3263CH/3300CH to 3363CH) is assigned.
The procedure to assign this area using CX-Programmer (version 6.0 or later) is explained below.
Take note that an I/O table for the PLC system is assumed to have been created in advance. For details,
refer to the operation manual for your PLC.
(1) Bring CX-Programmer online, and then change the mode to “Program.”
(2) Double-click

I/O Table/Unit Settings to open the I/O table.

(3) Click

Options (O) and then select Transfer [PLC

PC].

(4) Select

the

I/O table and high-function unit setting data check box, and then click Transfer.

(5) When the transfer result is displayed, check the result and then click OK.
(6) When the I/O table appears, right-click “CJ1W-DRM21” in the CPU rack, and then click Edit High-

function Unit Settings. The parameter edit window appears.

(7) Click

the

Clear Scan List switch and set “Clear Scan List.”

(8) Click

Transfer [PC

Unit] (T).

When the transfer is completed, the scan list is cleared and the seven-segment LEDs of the master
unit (CJ1W-DRM21) show the following display:







(9) In the parameter edit window, reset the Clear Scan List switch to “Off.”
(10) Set the Master Fixed Assignment Area Setting 1 switch to “Enable,” and then click Transfer [PC

Unit (T)].

(11) When the transfer is completed, reset the setting in (10) to “Off.”
(12) Set the Enable Scan List switch to “Enable,” and then click Transfer [PC

Unit (T)].

(13) When the transfer is completed, the scan list becomes effective and the left dot that was blinking in

(8) turns off. Fixed assignment is now completed.


Blinking Steady light