(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)
Signal Type
Bit
Signal name
Description
Details
Current
Position
32bits
Data
32-bit Signed Integer
The unit is 0.01mm.
(Example)
Read Value: 000003FF
H
= 1023 (decimal system) = 10.23mm
* When the value is read in hexadecimal notation, the negative figure
is expressed as a compliment of 2.
3.9 (3)
Command
Current
32bits
Data
32-bit Integer
It shows the current value in the current command.
The unit is mA.
Read Value: 000003FF
H
= 1023 (decimal system) = 1023mA
3.9 (3)
Current
Speed
32bits
Data
32-bit Signed Integer
It shows the current speed.
Positive Figure: Under movement in the opposite direction of the
home
Negative Figure: Under movement in the home direction
The unit is 0.01mm/sec.
(Example)
Read Value: 000003FF
H
= 1023 (decimal system) = 10.23mm/sec
* When it is read in hexadecimal notation, input the negative value
using a compliment of 2.
3.9 (3)
Alarm
code
16bits
Data
16-bit Integer
When an alarm is issued, the alarm code is output.
When any alarm is not issued, it is “0”.
Refer to the instruction manual for the controller main body for the
details of the alarms.
3.9 (3)
b15
EMGS
Emergency Stop: “ON” for Emergency Stop Status
3.7.7 (2)
b14
PWR
Controller Ready: “ON” for Ready
3.7.7 (1)
b13
ZONE2
Zone 2: “ON” for the current position within the zone set range
3.7.7 (12)
b12
ZONE1
Zone 1: “ON” for the current position within the zone set range
3.7.7 (12)
b11
䌐
ZONE
Position Zone:
“ON” when the current position is within the position zone set range
3.7.7 (12)
ACON
Unavailable (ON/OFF is undefined)
b10
PCON LOAD
Load Output Judgment
“ON” for Reached “OFF” for Not reached
(Refer to the instruction manual for the controller main body for more
information).
3.7.7 (26)
ACON
Unavailable (ON/OFF is undefined).
b9
PCON TRQS
Torque Level:
“ON” for Reached “OFF” for Not Reached
(Refer to the instruction manual for the controller main body for more
information).
3.7.7 (27)
b8
RMDS
Operation Mode Status:
“OFF” for currently “AUTO” mode, “ON” for currently “MANU” mode
3.7.7 (19)
b7
GHMS
Under Homing Operation: “ON” for Homing Operation
3.7.7 (6)
b6
PUSHS
Under Pressing Operation: “ON” for Pressing Operation
3.7.7 (25)
b5
PSEL
Pressing and a Miss: “ON” for pressing and a miss
3.7.7 (23)
b4
SV
Operation Ready: “ON” with Servo ON
3.7.7 (5)
b3
ALM
Alarm: “ON” with alarm issue
3.7.7 (3)
b2
MOVE
Movement Signal: “ON” with Actuator Movement
3.7.7 (9)
b1
HEND
Homing Completion: “ON” with Homing Completion
3.7.7 (6)
PLC Input
Status
Signal
b0
PEND
Positioning Completion Signal: “ON” with Positioning Completion
3.7.7 (10)