5. SCON-CA

CC-Link

161

5.4 Operation Mode Selection (Setting)

The operation mode is set using the parameters.
Set the mode toggle switch on the front surface of the controller to “MANU” side and set the parameter No. 84
“FMOD: Field Bus Operation Mode” using the personal computer application software (V8.00.00.00 or later)
(Refer to “5.10 CC-Link Related Parameters”).

Set Value

Operation Mode

Number of occupied stations

0: (Already set in system delivery)

Remote I/O Mode

1 Station

1

Position/Simplified Direct Value Mode

1 Station

2

Half Direct Value Mode

2 Stations

3

Full Direct Value Mode

4 Stations

4

Remote I/O Mode 2

1 Station

5

Position/Simplified Direct Value Mode 2

1 Station

6

Half Direct Value Mode 2

2 Stations

7

Remote I/O Mode 3

1 Station

8

Half Direct Value Mode 3

2 Stations

* Entering any value except for the ones described above will cause an “Excessive Input Value Error”.

Note: Set the Station Data for the Master Station to “ver.1 Remote Device Station”.

5.5 Station No. Setting

The Station No. is set using the parameters.
Set the parameter No. 85 “NADR: Field Bus Node Address” using the RC personal computer application
software.
(Refer to “5.10 CC-Link Related Parameters”).

Settable Range: 1 to 64 (Already set in system delivery)

Note: The PLC's CC-Link head I/O address is decided depending on the master unit installation position and the number

of I/O points occupied by the unit installed before it.
Following this head I/O address, the I/O addresses in PLC are allocated in order of the station No.
Also, for the details of the Station No. setting and I/O address setting in PLC, refer to the instruction manuals for the
master unit and loaded PLC.