5.10 CC-Link Related Parameters

The parameters related to CC-Link are from No. 84 to No. 87, 90 and 159.

Classification: C: External Interface Related

No Classification Symbol

Name

Default Value set in the Factory

before Delivery

1
°

83

Refer to instruction manual for

the controller for the parameters

No. 1 through No. 83.

84

C

FMOD Field Bus Operation Mode

0

85

C

NADR Field Bus Node Address

1

86

C

FBRS Filed Bus Communication

Speed

0

87

C

NTYP Network Type

1

90

C

CFMIO Filed Bus I/O Format

3

159

C

FBVS FB Half Direct Mode Speed Unit

0

z

Filed Bus Operation Mode (No. 84 “FMOD”)

The operation mode is set using the values 0 to 8 for the parameter No. 84.

Parameter No. 84

Set Value

Mode Name

Station Data and No. of

Occupied Stations

Description

0 (Set in delivery) Remote I/O Mode

Remote Device Station:

One Station

The operation is performed using the PIO

(24V I/O) through the CC-Link.

1

Position/Simplified

Direct Value Mode

Remote Device Station:

One Station

The target position can be set directly using

the value or the operation can be

performed using position data value.

The other values required for the operation

are set on the position data.

2

Half Direct Value

Mode

Remote Device Station:

Two Stations

In addition to the target position, the speed,

acceleration/deceleration and pressing

current value are set directly using the

values to perform the operation.

3

Full Direct Value

Mode

Remote Device Station:

Four Stations

All the values related to the position control

are set using the values to perform the

operation.

4

Remote I/O Mode 2 Remote Device Station:

One Station

The current position and current speed

reading functions are added to the

functions in the remote I/O mode.

5

Position/Simplified

Direct Value Mode 2

Remote Device Station:

One Station

Set this parameter in a case a force control

is necessary in the position/simple direct

mode.

6

Half Direct Value

Mode 2

Remote Device Station:

Two Stations

Set this parameter in a case a force control

is necessary in the half direct value mode.

7

Remote I/O Mode 3 Remote Device Station:

One Station

Set this parameter in a case a force control

is necessary in the remote I/O mode.

8

Half Direct Value

Mode 3

Remote Device Station:

Two Stations

Set this parameter in a case a switchover

of servo gain or anti-vibration control

parameter is necessary in the half-direct

mode.