Mx480 router cabinet requirements, An mx480 router chassis – Juniper Networks MX480 User Manual
Page 81
Figure 31: Clearance Requirements for Airflow and Hardware Maintenance
for an MX480 Router Chassis
Rear
Front
17.4"
(44.2 cm)
24.5"
(62.2 cm)
g004259
Front-mounting flange
19.2"
(48.7 cm)
24" (61 cm)
clearance required
for maintenance
24" (61 cm)
clearance required
for maintenance
Cable management system
27.75"
(70.75 cm)
Related
Documentation
MX480 Site Preparation Checklist on page 53
•
•
Installation Safety Warnings for Juniper Networks Devices on page 250
MX480 Router Cabinet Requirements
•
MX480 Router Cabinet Size and Clearance Requirements on page 57
•
MX480 Router Cabinet Airflow Requirements on page 58
MX480 Router Cabinet Size and Clearance Requirements
The minimum size cabinet that can accommodate the router is 482 mm wide and 800 mm
deep. A cabinet larger than the minimum requirement provides better airflow and reduces
the chance of overheating. To accommodate a single router, the cabinet must be at least
13 U high. If you provide adequate cooling air and airflow clearance, you can stack five
routers in a cabinet that has at least 48 U (84 in. or 2.13 m) of usable vertical space.
The minimum front and rear clearance requirements depend on the mounting
configuration you choose. The minimum total clearance inside the cabinet is 30.7 in.
between the inside of the front door and the inside of the rear door.
Related
Documentation
MX480 Site Preparation Checklist on page 53
•
•
MX480 Router Cabinet Airflow Requirements on page 58
•
Installation Safety Warnings for Juniper Networks Devices on page 250
57
Copyright © 2013, Juniper Networks, Inc.
Chapter 3: Preparing the Site for MX480 Router Installation