Fire Suppression Equipment
Type C fire extinguishers, which use noncorrosive fire retardants such as carbon dioxide
(CO
2
) and Halotron, are most effective for suppressing electrical fires. Type C fire
extinguishers displace the oxygen from the point of combustion to eliminate the fire. For
extinguishing fire on or around equipment that draws air from the environment for cooling,
use this type of inert oxygen displacement extinguisher instead of an extinguisher that
leave residues on equipment.
Do not use multipurpose Type ABC chemical fire extinguishers (dry chemical fire
extinguishers) near Juniper Networks devices. The primary ingredient in these fire
extinguishers is monoammonium phosphate, which is very sticky and difficult to clean.
In addition, in minute amounts of moisture, monoammonium phosphate can become
highly corrosive and corrodes most metals.
Any equipment in a room in which a chemical fire extinguisher has been discharged is
subject to premature failure and unreliable operation. The equipment is considered to
be irreparably damaged.
NOTE:
To keep warranties effective, do not use a dry chemical fire extinguisher
to control a fire at or near a Juniper Networks device. If a dry chemical fire
extinguisher is used, the unit is no longer eligible for coverage under a service
agreement.
We recommend that you dispose of any irreparably damaged equipment in an
environmentally responsible manner.
Related
Documentation
General Safety Guidelines for Juniper Networks Devices on page 245
•
•
General Safety Warnings for Juniper Networks Devices on page 246
•
General Electrical Safety Warnings for Juniper Networks Devices on page 264
•
DC Power Electrical Safety Warnings for Juniper Networks Devices on page 272
Installation Safety Warnings for Juniper Networks Devices
Observe the following warnings before and during hardware equipment installation:
•
Installation Instructions Warning on page 250
•
Rack-Mounting Requirements and Warnings on page 251
•
Installation Instructions Warning
WARNING:
Read the installation instructions before you connect the hardware
equipment to a power source.
Copyright © 2013, Juniper Networks, Inc.
250
MX480 3D Universal Edge Router Hardware Guide