Een (figure 61), Table 32 – Basler Electric BE1-11m User Manual
Page 97

9424200996 Rev L
85
Figure 61. Loss of Excitation - Reverse var Based Settings Screen
Table 32. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled or Enabled
n/a
n/a
Disabled
Pickup
0 or 1 to 6,000 (5A CTs)
0 or 1 to 1,200 (1A CTs)
varies
vars
0
Time Delay
0 or 1 to 600,000
varies
milliseconds
0
BE1-11m
Loss of Excitation - Reverse Var Based (40Q) Protection