59p - phase overvoltage protection, 59x - auxiliary overvoltage protection, 60fl - fuse loss – Basler Electric BE1-11m User Manual
Page 452: 62 - logic timers, 66 - starts per time interval protection

440
9424200996 Rev L
59P - Phase Overvoltage Protection
Pickup
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................
±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio ................................................ 98%
±1%
Timing Mode
Definite Timing
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................
±0.5% or ±2 cycles, whichever is greater
Inverse Timing
Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................
±5% or ±2 cycles, whichever is greater
chapter
for information on available timing curves.
59X - Auxiliary Overvoltage Protection
Pickup
Setting Range ........................................................... 1 to 150 V
Accuracy....................................................................
±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio ................................................ 98%
±1%
Timing Mode
Definite Timing
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................
±0.5% or ±2 cycles, whichever is greater
Inverse Timing
Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................
±5% or ±2 cycles, whichever is greater
chapter
for information on available timing curves.
60FL - Fuse Loss
Time Delay ................................................................ Fixed at 50 ms
62 - Logic Timers
Modes ........................................................................ Pickup/Dropout, One-Shot/Non-Retriggerable,
One-Shot/Retriggerable, Oscillator, Integrating
Timer, Latched
Setting Range ........................................................... 0 to 9,999,000 ms
Accuracy....................................................................
±0.5% or ±12 ms, whichever is greater
66 - Starts per Time Interval Protection
Time Interval
Setting Range ........................................................... 1 to 1,440 min
Accuracy....................................................................
±0.5%
Number of Starts
Setting Range ........................................................... 1 to 100
Specifications
BE1-11m