Pickup verification (3i0 mode) – Basler Electric BE1-11m User Manual
Page 369

9424200996 Rev L
357
Step 2: Prepare to monitor the 51-1 timings. Timing accuracy is verified by measuring the elapsed time
between a sensing current change and OUT1 closing.
Step 3: Connect a current source to BE1-11m terminals D1 and D2 (A-phase).
Step 4: Using the values listed in Table 149, apply the appropriate current values, and measure the
time between the application of current and the closure of OUT1. Record the results.
Step 5: Repeat step 4 for all of the current and time dial settings for your current sensing type.
Step 6: (Optional.) Repeat steps 1 through 5 for the B-phase and C-phase current inputs. Note: Be sure
to enable proper target for each phase being tested.
Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.
Step 8: (Optional.) Repeat steps 1 through 7 for 51-2, 51-3, 51-4, and 51-5.
Step 9: (Optional.) Repeat steps 1 through 8 with CT Circuit 2 as the source for protection systems
equipped with two sets of CTs. In step 3, replace D1 with F1, D2 with F2, etc.
Table 149. Timing Test Settings (Phase Mode)
Sensing Type
Time Dial
Applied Current
5 A
0.5
1.00 A
2.50 A
12.50 A
5.0
1.00 A
2.50 A
12.50 A
9.9
1.00 A
2.50 A
12.50 A
1 A
0.5
0.20 A
0.50 A
2.50 A
5.0
0.20 A
0.50 A
2.50 A
9.9
0.20 A
0.50 A
2.50 A
Pickup Verification (3I0 Mode)
Step 1: Use BESTCOMSPlus to send the operational settings in Table 150 to the BE1-11m. Reset all
targets.
BE1-11m
Inverse Overcurrent (51) Test