Basler Electric BE1-11m User Manual
Page 179

9424200996 Rev L
167
Reset will reset all logic alarms. Use the drag-and-drop method to connect a variable or series of
variables to the Reset input. The alarm reset logic blocks are shown in Figure 132.
Figure 132. Alarm Reset Logic Block
Major and Minor alarms can be cleared by pressing the Reset button on the front-panel interface while the
Alarms screen is being displayed or through BESTCOMSPlus. Alarms cannot be reset through the web
page interface.
Pressing the front-panel Reset key clears the alarms and the Major Alarm or Minor Alarm LED.
Depending on device security setup, a username and password may be required to reset alarms at the
front panel. Logging in is not required if the Unsecured Access Level is set to Operator or higher, as long
as no other port has access higher than Read. Alarm reset can also be set outside of security control,
allowing reset without logging in. Refer to the
chapter for more information.
An alarm reset is available as a status input in BESTlogicPlus. Refer to the
chapter for
more information.
BE1-11m
Alarms