Remote rtd metering, Een (figure 65), N table 36 – Basler Electric BE1-11m User Manual
Page 105

9424200996 Rev L
93
Figure 65. Resistance Temperature Detector Settings Screen
Table 36. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled, Over, Under,
or Over & Under
n/a
n/a
Disabled
Source
RTD Group 1 to RTD Group 7
n/a
n/a
RTD Group 1
Over Pickup
32 to 482 degrees F
or 0 to 250 degrees C
Calculated (F)
1 (C)
degrees
32
Under Pickup
32 to 482 degrees F
or 0 to 250 degrees C
Calculated (F)
1 (C)
degrees
32
Time Delay
0 to 600,000
varies
milliseconds
0
Voting
1 to 24
1
units
1
Remote RTD Metering
RTD metering values are obtained through BESTCOMSPlus by using the Metering Explorer to open the
Analog Metering, RTD Meter tree branch. BESTCOMSPlus must be online with the BE1-11m to view RTD
metering. Alternately, values can be obtained through the front-panel display by navigating to the
Metering, Analog Metering, RTD Meter Input screen.
BE1-11m
Resistance Temperature Detector (49RTD) Protection