Irig interface, Real-time clock – Basler Electric BE1-11m User Manual
Page 457

9424200996 Rev L
445
Input Burden
Burden values shown in Table 191 assume nominal value of input voltage applied.
Table 191. Contact-Sensing Input Burden
Style Option
Nominal Input Voltage
Burden
Jumper Installed
(Low Position)
Jumper Not Installed
(High Position)
Mxx1xxxxxxxxxx
48 Vdc or 125 Vac/dc
22 k
Ω
53 k
Ω
Mxx2xxxxxxxxxx
125/250 Vac/dc
66 k
Ω
123 k
Ω
Mxx3xxxxxxxxxx
24 Vdc
n/a
6 k
Ω
Recognition Time
Programmable ........................................................... 4 to 255 ms
Note
All timing specifications are for the worst-case response. This includes
output contact operate times and standard BESTlogicPlus operation
timing but excludes input debounce timing and nonstandard logic
configurations. If a nonstandard logic scheme involves feedback, then
one or more BESTlogicPlus update rate delays must be included to
calculate the worst-case delay. An example of feedback is logic
outputs driving logic inputs. For more information, see BESTlogicPlus.
Terminals
IN1 ............................................................................. B1, B2
IN2 ............................................................................. B3, B4
IN3 ............................................................................. B5, B6
IN4 ............................................................................. B7, B8
IN5 ............................................................................. E1, E2
IN6 ............................................................................. E3, E4
IN7 ............................................................................. E5, E6
IRIG Interface
Interface supports IRIG Standard 200-04, Format B006.
Input Signal ............................................................... Demodulated dc. Level-shifted, digital signal
Input Voltage Range .................................................
±10 Vdc maximum
Input Resistance ....................................................... Nonlinear, approximately 4 k
Ω at 3.5 Vdc,
approximately 3 k
Ω at 20 Vdc
Terminals................................................................... A1, A2
Logic Voltage Threshold
High ........................................................................... 3.5 Vdc minimum
Low ............................................................................ 0.5 Vdc maximum
Real-Time Clock
Clock has leap year and selectable daylight saving time correction. Backup capacitor and standard
backup battery sustain timekeeping during losses of BE1-11m operating power.
Resolution ................................................................. 1 s
Accuracy....................................................................
±1.73 s/d at 25°C
BE1-11m
Specifications