Timing verification – Basler Electric BE1-11m User Manual
Page 402

390
9424200996 Rev L
Timing Verification
Time Delay Range = 0 ms or 50 to 600,000 ms
Timing Accuracy =
±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
60,000 ms
59,700 ms
60,300 ms
P / F
5
0 ms
0 ms
34 ms
P / F
5
50 ms
17 ms
84 ms
P / F
Power Factor (55) Test
BE1-11m