Basler Electric BE1-11m User Manual
Page 551

9424200996 Rev L
539
●
FIELD
○
Excitation (Brushless) .......................................22 kW @ 51 Vdc
○
No Load Saturation
■
P.U. Line Volts
0.25
0.50
0.75
1.00
1.10
1.20
1.30
■
Field Amps
34.3
68.9
105.9 144.4 161.8 181.8 213.5
(motor)
0.3
0.7
1.1
1.3
1.5
1.6
1.9
(exciter)
○
Rated P.F. Excitation
■
P.U. Load
0.25
0.50
0.75
1.00
1.15
■
Field Amps
189.1 248.3 314.3 384.9 429.4
(motor)
1.7
2.2
2.9
3.5
4.6
(exciter)
●
RTDs
○
Six Stator RTDs ................................................100
Ω, 3-wire element, platinum
○
Two Bearing RTDs ...........................................100
Ω, 3-wire element, platinum
○
One Ambient RTD ............................................100
Ω, 3-wire element, platinum
●
STARTING
○
Minimum Starting Voltage ................................85%
○
Starting Performance
■
Starting Torque ....................................52%
■
Pull-In Torque ......................................115%
■
Pull-Out Torque ...................................151%
■
Inrush ...................................................368%
■
Pull-In Slip............................................5%
■
Accelerating Time ................................2.4 seconds
■
Motor WK
2
............................................8391
■
Load WK
2
.............................................752
Table 200 lists the allowable time on the squirrel cage winding at 100% voltage.
Table 200. Allowable time on Squirrel Cage Winding at 100 Percent Voltage
% Speed
0
50
75
95
Seconds
16.7
25
34
288
○
Acceleration Time to Synchronous Speed (100% V) .............. 2.42 seconds
○
Acceleration Time to Synchronous Speed (85%) V) ............... 4.27 seconds
○
Power Factor relay (55) for pullout 0.90 P.F. lag; locked out until after 2.5 seconds
●
CONSECUTIVE STARTS
○
Ambient Temperature .................................... 2 starts
■
Idle Starts Time ................................ 60 minutes
■
Running Starts Time ......................... 30 minutes
○
Operating Temperature ................................. 1 start
■
Idle Starts Time ................................ 90 minutes
■
Running Starts Time ......................... 60 minutes
●
THERMAL TIME CONSTANT
○
Ambient (Stopped Condition) ........................ 190 minutes
○
Operating (Running Condition) ...................... 60 minutes
●
RUNNING
○
Ride-Through Minimum Voltage .................... 75% for 30 seconds
○
Bearing Alarm Temperature .......................... 90
°C
○
Bearing Trip Temperature ............................. 95
°C
BE1-11m
Settings Calculation Examples