N figure 257 – Basler Electric BE1-11m User Manual
Page 364

352
9424200996 Rev L
•
Fault recording is enabled.
•
Breaker Status is closed with /IN1.
Figure 257. BESTlogicPlus Settings (BFI52 Contact Initiate)
Step 3: IN1 is used to simulate breaker status as supplied by a “b” contact from the circuit breaker. With
no wetting voltage applied to BE1-11m input IN1, the BE1-11m considers the breaker closed
because of the /IN1 designation at the breaker status input of the breaker failure element. A
switched wetting voltage at IN2 is used to simulate an external BFI52 initiate contact for starting
the Breaker Failure Timer. This input is also used to start the test set timer and OUT1 of the
BE1-11m is used to stop the test set timer. OUT2 should be monitored to verify operation of the
re-trip circuit upon breaker failure initiate.
Step 4: With no wetting voltage applied to BE1-11m input IN1, switch on the wetting voltage to IN2 and
measure the operate time. Record the result.
Step 5: Apply wetting voltage to IN1 and repeat step 4. There should be no operation.
Step 6: Repeat step 3 with the delay timer set at 200 ms and 300 ms. Record the results.
The following tests are for Current Supervised BE1-11m trip initiates. Any or all BE1-11m trips can be
used: 50 Trip, 51 Trip, etc. For ease of testing, the 50-1 Trip variable will be used in the following tests.
Step 7: Use BESTCOMSPlus to send the operational settings in Table 144 to the BE1-11m. Reset all
targets.
Table 144. Operational Settings (BFI50 Current Supervised BE1-11mTrip Initiate)
Setting
Value
BESTCOMSPlus Screen
Description
Element
Mode
Enabled
Protection, Current, Breaker Fail (50BF)
Enables 50BF function
Phase
Pickup
1 A
Protection, Current, Breaker Fail (50BF)
Sets phase pickup to 1 A
Ground
Pickup
1 A
Protection, Current, Breaker Fail (50BF)
Sets ground pickup to 1 A
Control
Timer
0
Protection, Current, Breaker Fail (50BF)
Sets control timer to 0
Delay
Timer
100 ms
Protection, Current, Breaker Fail (50BF)
Sets delay timer to 100 ms
50BF
Enabled
Target Configuration, Targets
Enables target for 50BF
Breaker
Fail
Minor, Non-
Latching
Alarm Configuration, Alarms
Sets 50BF BFI alarm for Minor
Alarm
Element
Mode
IA
Protection, Current, Instantaneous
Overcurrent (50-1)
Enables 50-1 function
Breaker Fail (50BF) Test
BE1-11m