Operational settings, N table 76 – Basler Electric BE1-11m User Manual
Page 205

9424200996 Rev L
193
Table 76. Logic Output
Name
Logic Function
Purpose
Fuse Loss
Output
True when the 60FL logic is true
Operational Settings
Fuse loss element operational settings are configured on the Fuse Loss (60FL) settings screen (Figure
156) in BESTCOMSPlus. Settings are summarized in Table 77.
Figure 156. Fuse Loss Settings Screen
Table 77. Operational Settings
Setting
Purpose
Block Voltage Control (51/27)
When enabled and the 60FL logic is true (voltage sensing is lost),
the current tripping level is controlled by the 51 function and the
27R function is inhibited. When enabled and the 60FL logic is
false, the current tripping level is controlled by the 51/27R
function.
Block Phase/V1 Voltage
Elements
All functions that use phase voltage (P) and positive-sequence
voltage (V1) measurements are blocked when the 60FL logic is
true. (27 and 59)
Block 3V0 Voltage Elements
All functions that use the 3-phase residual voltage (3V0)
measurement are blocked when the 60FL logic is true. (59X - 3V0
mode)
Block V2 Voltage Elements
All functions that use the negative-sequence voltage (V2)
measurement are blocked when the 60FL logic is true. (59X - V2
mode)
Block Power/Power Factor
Elements
All functions that use the power measurements are blocked when
the 60FL logic is true. (32 and 55)
Ignore Breaker Status
When enabled, breaker status is ignored.
BE1-11m
Fuse Loss (60FL)