Timing verification (standard curve) – Basler Electric BE1-11m User Manual
Page 411

9424200996 Rev L
399
Timing Verification (Standard Curve)
Time Dial Range = 1 to 20
Timing Accuracy =
±5% or ±2½ cycles, whichever is greater
Step
Time Dial
Applied Current
Low
Actual Timing
High
Pass/Fail
7
10
10 A
34.409 sec
38.031 sec
P / F
11
10
10 A
30.276 sec
33.463 sec
P / F
Timing Verification (Standard Curve with Emergency Start)
Time Dial Range = 1 to 20
Timing Accuracy =
±5% or ±2½ cycles, whichever is greater
Step
Time Dial
Applied Current
Low
Actual Timing
High
Pass/Fail
17
10
10 A
68.818 sec
76.062 sec
P / F
Timing Verification (Standard Curve with RTD Biasing)
Time Dial Range = 1 to 20
Timing Accuracy =
±5% or ±2½ cycles, whichever is greater
Step
Time Dial
Applied Current
Low
Actual Timing
High
Pass/Fail
22
10
10 A
29.934 sec
33.085 sec
P / F
BE1-11m
Thermal Curve (49TC) Test