Figure 70), N table 39 – Basler Electric BE1-11m User Manual
Page 113

9424200996 Rev L
101
Figure 70. Thermal Curve Settings Screen
Table 39. Operational Settings
Setting
Range
Increment
Unit of
Measure
Default
Mode
Disabled, Standard Curve, IEC
Curve, or User Curve
n/a
n/a
Disabled
RTD Biasing
*
Disabled or Enabled
n/a
n/a
Disabled
RTD Source
*
RTD Group 1 to RTD Group 4
n/a
n/a
RTD
Group 1
Standard Curve
Time Dial
1 to 20
0.01
units
1
K
0 to 20
0.01
units
1
IEC Hot Curve Current
0 to 25 (5A CTs)
0 to 5 (1A CTs)
0.001
amps
0
IEC Curve
Time Constant
1 to 10,000
1
seconds
1
Overload
0.9 to 1.2
0.01
units
1
Max Emergency
Thermal Capacity
0 or 150 to 1,000
1
percent
0
Running Cool
Time Constant
1 to 1,000
0.01
minutes
1
Stopped Cool
Time Constant
1 to 1,000
0.01
minutes
1
Hot Safe Stall Time
1 to 2,000
0.1
seconds
0
Cold Safe Stall Time
1 to 2,000
0.1
seconds
0
* For use when an optional RTD module is connected.
BE1-11m
Thermal Curve (49TC) Protection