Sensing transformers settings, Ct setup β Basler Electric BE1-11m User Manual
Page 298

286
9424200996 Rev L
Setting
Range
Increment
Unit
Default
Nominal Aux
Voltage
50 to 300
0.01
volts
69.3
Power Polarity
Normal or Reverse
n/a
n/a
Normal
Phase Rotation
ABC or ACB
n/a
n/a
ABC
Full Load Amps
1 to 25 (%A CTs)
0.2 to 5 (1A CTs)
0.001
amps
1
Service Factor
1 to 1.4
0.01
units
1
Motor Start
Detection
Current Only, Current and Contacts, or
Contacts Only
n/a
n/a
Current
Only
Motor Stop
Detection
Current Only, Current and Contacts, or
Contacts Only
n/a
n/a
Current
Only
Sensing Transformers Settings
The BE1-11m requires information about the current and voltage transformers to provide metering, fault
reporting, and protective relaying.
Sensing transformer settings are configured on the Sensing Transformers settings screen in
BESTCOMSPlus. A summary of the settings appear at the end of this section.
BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Sensing Transformers
HMI Navigation Path: Settings Explorer, System Parameters, Sensing Transformers
CT Setup
The BE1-11m requires setting information on the CT ratios. This setting is used by the metering and fault
reporting functions to display measured quantities in primary units.
Unbalanced Calculation Method
Unbalanced overcurrent protection is provided by the 50 and 51 elements. Two methods are available to
calculate unbalanced current.
Method 1 (I2/I1)
πΌ
πππππππππ
=
πΌ
2
πΌ
1
Γ MIN
where:
MIN =
πΌ
π΄π£πππππ
πΌ
π ππ‘ππ
or 1, whichever is less
Method 2 (Average)
πΌ
πππππππππ
=
οΏ½MAXp β I
π΄π£πππππ
οΏ½ or οΏ½I
π΄π£πππππ
β MINpοΏ½, whichever is greater
I
π΄π£πππππ
Γ MIN
where:
MIN =
πΌ
π΄π£πππππ
πΌ
π ππ‘ππ
or 1, whichever is less
MAXp = maximum of all three phases
MINp = minimum of all three phases
Configuration
BE1-11m