N figure 352 β Basler Electric BE1-11m User Manual
Page 539

9424200996 Rev L
527
Figure 352. Protection, Current, Instantaneous Overcurrent (50-1) Screen
Instantaneous Overcurrent (50-2) - Ground Fault Protection
The system is solidly grounded so that a ground fault draws current in the magnitude of a three-phase
fault per IEEE C37.96-2000, IEEE Guide for AC Motor Protection. To determine the three-phase fault
current, consider that the motor subtransient reactance of 0.15 is the limiting impedance. The pickup
setting is calculated using Equation 44. A pickup setting of 1/3 of the instantaneous three-phase fault
current is recommended per IEEE C37.96-2000, IEEE Guide for AC Motor Protection.
πππππ’π = οΏ½
1
π"π
β
πΉπΏπ΄
πΆπ π ππ‘ππ
οΏ½ β
1
3
= οΏ½
1
0.15
β
363
80
οΏ½ β
1
3
= 10.08 π΄ π ππππππππ¦
Equation 44. 50-2 Pickup
Select 3I0 (residual) mode and set the Pickup setting to 10.08 A as shown in Figure 353.
Figure 353. Protection, Current, Instantaneous Overcurrent (50-2) Screen
Instantaneous Overcurrent (50-3) - Unbalance Protection
The NEMA MG-1 standard states that the existence of unbalanced voltage feed results in four to 10 times
the current imbalance. The negative-sequence voltage unbalances should not exceed 5 percent. This
application uses negative-sequence current as the input to an overcurrent element to sense unbalance
conditions. For conservative protection, choose 4
β’ 5%, which is 20 percent imbalance. A 10 second
delay is appropriate because the heating is slow (motor mass is large). The pickup setting calculation is
shown in Equation 45.
πππππ’π = ππππ ππ‘ππππππ (5%) β πΆπππ πππ£ππ‘ππ£π ππππ‘πππ‘πππ (4) β πΉπΏπ΄
πππππππππ¦
= 0.05 β 4 β 4.54 = 0.908 π΄ π ππππππππ¦
Equation 45. 50-3 Pickup
Select I2 mode, set the Pickup setting to 0.908 A, and set the Time Delay to 10 seconds as shown in
Figure 354.
BE1-11m
Settings Calculation Examples