Retrieving oscillographic records, O table 61, N figure 118 – Basler Electric BE1-11m User Manual
Page 166

154
9424200996 Rev L
Figure 118. Fault Records Screen
Table 61 summarizes the oscillographic records settings.
Table 61. Oscillographic Records Settings
Setting
Range
Increment
Default
Sample Resolution
32, 16, or 8
n/a
32
Number of Records to Store
32, 16, 8, or 4
n/a
32
Prefault Cycles
0 to 16
1
2
Retrieving Oscillographic Records
Oscillographic records can be downloaded through the Reports, Fault Reports screen in BESTCOMSPlus
(Figure 117). See Fault Reports earlier in this chapter. Oscillographic records can also be downloaded
through the web page interface. For more information, refer to the
chapter.
Fault Reporting
BE1-11m