Operational settings – Basler Electric BE1-11m User Manual
Page 145

9424200996 Rev L
133
Figure 97. Setting Group Logic Block
Table 55. Logic Inputs and Outputs
Name
Logic
Function
Purpose
Automatic
Input
True when automatic control is enabled and false when logic
control is enabled
D0, D1, D2, D3
Inputs
Meaning depends upon the Mode setting
SG0, SG1, SG2, SG3
Outputs
True for the active setting group
SGCACTIVE
Output
True when Setting Group Control is Active
SGCLOVRD
Output
True when Setting Group Control is overridden by logic
Operational Settings
Setting group operational settings are configured on the Setting Group Setup screen (Figure 98) in
BESTCOMSPlus. Setting ranges and defaults are summarized in Table 56.
BE1-11m
Setting Groups