Functional test report, Pickup verification, Timing verification – Basler Electric BE1-11m User Manual
Page 349

9424200996 Rev L
337
Step 2: Prepare to monitor the 37 timings. Timing accuracy is verified by measuring the elapsed time
between a sensing current change and OUT1 closing.
Step 3: Connect a current source and apply 0.55 Aac to terminals D1 and D2 (A-phase).
Step 4: Step the current down to 0.45 A. Measure the time delay and record the result.
Step 5: Repeat step 4 for the 5000 ms and 10000 ms time delay settings of Table 130. Record the
results.
Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.
Step 7: (Optional.) Repeat steps 1 through 6 with CT Circuit 2 as the source for protection systems
equipped with two sets of CTs. In step 3, replace D1 with F1, D2 with F2, etc.
Functional Test Report
Pickup Verification
Pickup Setting Range = 0.5 to 100 A for 5A sensing
0.1 to 20 A for 1A sensing
Pickup Accuracy =
±2% or ±50 mA, whichever is greater for 5A sensing
±2% or ±10 mA, whichever is greater for 1A sensing
Dropout should occur between 101-107% of the actual pickup value.
Step
Pickup Setting
Low
Actual Pickup
High
Low
*
Actual Reset
High
*
Pass/Fail
6
0.5 A (5A CT)
0.45 A
0.55 A
0.505 A
0.535 A
P / F
7
5.0 A (5A CT)
4.9 A
5.1 A
5.05 A
5.35 A
P / F
7
20.0 A (5A CT)
20.6 A
20.4 A
20.2 A
21.4 A
P / F
6
0.1 A (1A CT)
0.09 A
0.11 A
0.101 A
0.107 A
P / F
7
1.0 A (1A CT)
0.98 A
1.02 A
1.01 A
1.07 A
P / F
7
4.0 A (1A CT)
3.92 A
4.08 A
4.04 A
4.28 A
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification
Time Delay Range = 0 to 60000 ms
Timing Accuracy =
±0.5% or ±½ cycle, whichever is greater + 3 cycles max for currents 1.5 x pickup
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2000 ms
1942 ms
2058 ms
P / F
5
5000 ms
4927 ms
5073 ms
P / F
5
10000 ms
9902 ms
10098 ms
P / F
BE1-11m
Instantaneous Undercurrent (37) Test